Hlorogen H4000

hlorogen_mali150Hlorogen is device for electrolytic production of chlorine in the form of sodium hypochlorite (NaOCl) solution.
Capacity is 4 kg/h or 96 kg/day of equivalent chlorine.

Since no gaseous chlorine is present, water chlorination is absolutely safe due to system design. For production of sodium hypochlorite solution all that is needed is  common salt,  softened  water and electric energy. Production expenses are up to two times lower compared  to gaseous chlorine disinfection, or commercial sodium hypochlorite.

System is easy to use, demands only minimal maintenance and it is fully automated. Exploitation period is minimum 20 years.

Characteristics of the system

Hlorogen H2000 – Characteristics of the system

Four E1000 electrolyzers capacity to produce 4000g/h, 96.0 kg/day is sufficient to disinfect the water with flow of 2222 l/s in order to maintain the 0.5 mg/l residual prescribed by law.

Maximum water flow that can be disinfected with Hlorogen H2000, depending on chlorine needs and desired residuals

Chlorine need (mg/l)

Desired chlorine residual (mg/l)

Chlorine consumption (g/min)

NaOCl consumption (ml/min)

Chlorine consumption (g/h)

NaOCl consumption (l/h)

Maximal water flow (l/s)

0

0,3

66,67

6667

4000

400

3704

0

0,4

66,67

6667

4000

400

2778

0

0,5

66,67

6667

4000

400

2222

0,1

0,5

66,67

6667

4000

400

1852

0,2

0,5

66,62

6662

3996

399,6

1586

0,3

0,5

66,62

6662

3996

399,6

1388

0,4

0,5

66,64

6664

3998

399,8

1234

0,5

0,5

66,6

6660

3996

399,6

1110

0,6

0,5

66,67

6667

4000

400

1010

0,7

0,5

66,67

6667

4000

400

926

0,8

0,5

66,62

6662

3996

399,6

854

0,9

0,5

66,52

6652

3992

399,2

792

1

0,5

66,6

6660

3996

399,6

740

1,2

0,5

66,5

6650

3990

399

652

1,4

0,5

66,58

6658

3994

399,4

584

1,6

0,5

66,52

6652

3992

399,2

528

1,8

0,5

66,52

6652

3992

399,2

482

2

0,5

66,6

6660

3996

399,6

444

2,2

0,5

66,58

6658

3995

399,5

411

2,4

0,5

66,64

6664

3999

399,9

383

2,6

0,5

66,58

6658

3996

399,6

358

2,8

0,5

66,52

6652

3992

399,2

336

3

0,5

66,57

6657

3994

399,4

317

3,5

0,5

66,48

6648

3988

398,8

277

4

0,5

66,42

6642

3985

398,5

246

4,5

0,5

66,6

6660

3996

399,6

222

5

0,5

66,67

6667

4000

400

202

 

 

Technical Data

This content is for our users only. Register here. If you already have an account, you can log in here.
 

Operation Basics

Hlorogen H4000 – Operation Basics

Water from the pipeline is filling water softener (4), calcium and magnesium ions are removed, and on the outlet of the softened water is obtained. Dosing pump (6) is transferring this water to the electrolyser where it is mixed with sodium chloride solution transferred from tank (3) by means of another dosing pump ( tank 3 contains saturated sodium chloride solution). Electrochemical reaction which results in conversion of sodium chloride into sodium hypochlorite is taking place in the electrolyser cell energized by direct electric current from energetic assembly (35) of the Hlorogen device Hypochlorite solution is stored in the tank (2). Hydrogen generated by conversion reaction is let in to atmosphere by means of ventilating system (28). Optimal hypochlorite production is achieved using system automatic arrangement (36). Sodium hypochlorite solution is injected by dosing membrane pumps (38) into pipeline with water to be disinfected. Residual chlorine analyzer (39) connected into regulation circuit with dosing pump keeps the concentration of residual chlorine in the water on the predetermined level. This is providing continuous production of disinfecting agent, automatic process control and automatic dosing and residual chlorine control.

Full system operation can be monitored through PC (37).

TECHNOLOGICAL SCHEME OF HLOROGEN PLANT

HLOROGEN_tehnoloska_sema

 

Download

This content is for our users only. Register here. If you already have an account, you can log in here.
 
 

Back